Emrik Strandh & Lei Wang
International Journal of Heat and Fluid Flow, Vol 122, Dec 2026
Department of Energy Sciences, Lund University, Lund, Sweden
DOI:10.1016/j.ijheatfluidflow.2026.110744
Keywords: Heat transfer; Infrasonic standing waves; Acoustic particle velocities; Frequencies; Power consumption
Abstract
Experimental studies were performed to investigate the heat transfer from a hot plate in a cooling chamber which is subjected to resonant infrasonic standing waves. The tested frequencies of infrasound were varied between 5.3 and 13.1 , and the pressure amplitudes ranged from 10.2 to 27.6 , which corresponds to the particle velocity in the cooling chamber between 13.6 and 36.9 . The results indicated that the convective heat transfer coefficient is mainly affected by the magnitude of , while the dependence of the frequency is rather weak. In the test range, the measured heat transfer coefficients varied from 55 to 140 . Compared to natural convection, it was found that infrasound waves enhance heat transfer by a factor of . Based on the data fitting, an empirical correlation is proposed to predict the mean convective heat transfer coefficient from the hot plate, that is, . In addition, we observed that the power consumption in the infrasonic cooling system was roughly proportional to the square of the particle velocity. These results are helpful for industries to develop advanced infrasound coolers.